Y8610U4001 Electronic Ignition Retrofit Kit
Electronic Ignition Retrofit Kit
Intermittent Pilot Retrofit Kits save energy by converting atmospheric standing pilot systems to intermittent pilot. Typical applications are gas-fired atmospheric furnaces, boilers and heating appliances. (For 150,000 BTU units)
Specifications
- Description: Provide electronic control of intermittent pilot ignition systems used on gas fired furnaces, boilers, and other heating appliances.
- System Type: Intermittent Pilot
- Ignition Sequence: Continuous retry, after trial for ignition, pilot gas shuts off for 5 minutes, then another trial for pilot ignition takes place
- Typical Gas Control: VR8204
- Type of Gas: Natural or LP
- Flame Sense: Single Rod or Two Rods
- Ignition Source: Internal high voltage spark generator
- Prepurge: 0 or 30 seconds
- Ignition trials to lockout: continuous retry
- Lockout Timing: 15 or 90 seconds
Features
- Y8610U kits are for use with natural or LP gas: provides 100 percent pilot gas shutoff if pilot fails to light; after 6-minute delay, trial for ignition is repeated.
- Ignition trail/delay sequence is repeated until the appliance lights or call for heat is removed.
- Includes gas valve, ignition module, pilot burner hardware, ignition cable, and wiring harness
- heat is removed.
- heat is removed.
- Includes gas valve, ignition module, pilot burner hardware, ignition cable, and wiring harness