Gas Valve SV9520H8513 24v 1/2" X 1/2" Direct Hot Surface Ignition Smartvalve Control with fast-slow Opening and 3.5 in. wc pressure Regulator setting Includes Lp Kit
Gas Valve
SV9520H8513 24v 1/2" X 1/2" Direct Hot Surface Ignition Smartvalve Control with fast-slow Opening and 3.5 in. wc pressure Regulator setting Includes Lp Kit
Part Description:
- Gas Valve
- Type Fast-Slow Opening, Straight-Through
- Nominal Size 1/2 Inch
- End Connection Threaded x Threaded
- End to End Distance 3.2 Inch
- Input Supply Rating 24 Volt AC at 50/60 Hertz
- Temperature Rating -40 to 175 Deg F
- Pressure Rating 1/2 PSI
- Inclusions/Features Natural to Liquid Propane Conversion Kit
- Application Rooftop Furnace, Boiler, Unit/Infrared/Water Heater, Commercial Cooking Appliance
- Applicable Standard CSA
- Overall Dimension 4.1 Inch Length x 4.9 Inch Height
- Ignition Type Intermittent Hot Surface Pilot
- Flame Failure Response Time 2 Second at 5 Microamp
- Ignition Trial Time 7 Second
- Prepurge Time 15 Second
- Pressure Tapping 1/8 Inch Threaded
- Pressure Regulator Set Point 3.5 Inch WC
- Mounting 0 to 90 Degree Vertical Installation
Part Number: SV9520H8513/U
Features / Benefits
- The Smartvalve System Controls Combine Gas Flow Control and Electronic Direct Main Burner Ignition Sequencing Functions into a Single Unit
- The Ignition Source is 120 Volt Hot Surface Igniter Lighting the Main Burner Flame
- Provides All Gas Ignition Safety Functions by Controlling Gas Flow, Ignition Source and a 120 Volt AC Combustion Air Blower
- The Control also Monitors the Appliance Airflow Proving Switch Circuit and Limit String to Assure Proper Appliance Operation
- The Control Communicates Directly with the St9160 Electronic Fan Timer (Eft) in Typical Forced Warm Air Furnace Applications
- It Can Directly Interface with the Appropriate Power Supplies and a System Thermostat for Additional Appliance Applications
- When Controlled Directly by a Thermostat, the Control Does Not Provide a Postpurge Function, as Power to the Control is Removed When the Thermostat Call for Heat End
Specifications
MANUFACTURER | HONEYWELL RESIDENTIAL |
MANUFACTURER PART NUMBER | SV9520H8513/U |
METROPAC INTERNAL PART NUMBER | 109363 |
ADDITIONAL INFORMATION | Overall Dimension 4.1 Inch Length x 4.9 Inch Height; Ignition Type Intermittent Hot Surface Pilot; Flame Failure Response Time 2 Second at 5 Microamp; Ignition Trial Time 7 Second; Prepurge Time 15 Second; Pressure Tapping 1/8 Inch Threaded; Pressure Regulator Set Point 3.5 Inch WC; Mounting 0 to 90 Degree Vertical Installation |
MARKETING TEXT | The SmartValve System Controls combine gas flow control and electronic direct main burner ignition sequencing functions into a single unit. The ignition source is 120V hot surface igniter lighting the main burner flame. Provides all gas ignition safety functions by controlling gas flow, ignition source, and a 120 Vac combustion air blower. The control also monitors the appliance airflow proving switch circuit and limit string to assure proper appliance operation. The SmartValve System Controls provide prepurge, postpurge and timed trial for ignition with multiple ignition trials and auto reset from lockout. Diagnostic LED indicates system status. |
PRODUCT NAME | Gas Valve |