626404R Nordyne Rollout Limit Switch Double Pole
626404R Nordyne Rollout Limit Switch
Product Overview
626404R is an OEM double-pole rollout limit switch rated at 145°F (L145) for Nordyne HVAC systems. It serves as a critical safety device by interrupting the electrical circuit when temperatures exceed the specified limit, preventing overheating and potential component damage.
Technical Specifications
-
Opens at 145°F limit point (L145)
-
Double-pole configuration interrupting both hot and neutral lines
-
Size: 64TX11 mounting footprint for direct OEM replacement
Cross-Reference Part Numbers
| 626404R | Replaces: 208439, 626257, 6262570, 626261, 6262610, 626334, 626404 |
Compatibility
Compatible with Nordyne and Intertherm gas furnaces and packaged HVAC units requiring a 145°F double-pole rollout limit switch. Always verify the part number on the appliance’s data plate or service manual before ordering.
Technician Notes
-
De-energize all power sources; lock out/tag out per safety procedures.
-
Remove the furnace access panel to locate the existing rollout limit switch.
-
Document or label each lead on the old switch before disconnecting.
-
Remove mounting screws and carefully extract the old switch.
-
Align the new 626404R on the same mounting holes and secure with screws.
-
Reconnect the wiring to the corresponding terminals, ensuring firm, corrosion-free connections.
-
Restore power and allow the system to call for heat; the circuit remains closed below 145°F and opens at the limit point.
-
If the switch trips prematurely or fails to reopen, inspect the heat exchanger and airflow for blockages before replacing components.
2 pole limit control switch. L145F (L145-40F). Size 64TX11. Double Pole Limit Switch
Replaces 208439, 626257, 6262570, 626261, 6262610, 626334 & 626404.