632445R Nordyne PRESSURE SWITCH -1.10"WC SPST

632445R Nordyne PRESSURE SWITCH -1.10"WC SPST

  • $ 34.19
    Unit price per 
  • Save $ 5.61
Shipping calculated at checkout.


632445R Nordyne Pressure Switch –1.10″ W.C. SPST


Product Overview

The 632445R Nordyne Pressure Switch is a direct-fit OEM replacement engineered to monitor inducer motor airflow and safeguard furnace operation. Factory-set to trip at –1.10″ W.C. with an SPST contact configuration, it delivers precise, repeatable actuation for consistent system performance.


Technical Specifications

Parameter Specification
Setpoint (Trip Pressure) –1.10″ W.C. (nominal)
Pressure type Differential vacuum
Switch configuration SPST (normally open until trip)
Proof pressure 2.5″ W.C. (maximum)
Burst pressure 5.0″ W.C. (maximum)
Electrical rating 1 A @ 120 VAC (resistive)
Connection fitting 1/8″ hose barb
Housing material High-impact thermoplastic
Terminals ¼″ quick-connect spades
Operating temperature range –40 °F to 180 °F (–40 °C to 82 °C)
Mounting style Snap-in or bracket mountable
Dimensions (L × W × H) 1.9″ × 1.2″ × 1.3″ (48 × 30 × 33 mm)
Weight 0.10 lb (45 g)


Cross-Reference Part Numbers

  • Nordyne 632445R

  • Neuco 632445R

  • Coleman 632445R

  • Robertshaw PS181

  • White-Rodgers 36D47

  • OEM equivalent for Bosch-era furnaces


Compatibility

  • Nordyne/Coleman N5, N6, P5, P6 series furnaces

  • York/Westinghouse standard and high-efficiency units

  • Goodman/Amana GSX and GMV series furnaces

  • Bryant/Payne single-stage and 80% AFUE models

  • American Standard Basic Heat and Performance lines

  • Any HVAC system designed for a –1.10″ W.C. pressure switch


Technician Notes

  • Disconnect power and verify zero voltage before servicing.

  • Use clean, flexible tubing and secure it firmly to the inlet barb—avoid kinks.

  • Mount the switch in the original location and orientation to preserve calibration.

  • Test actuation with a calibrated manometer or vacuum pump: continuity should close at –1.10″ W.C. and open when vacuum is released.

  • Inspect tubing and clamps for wear; replace if cracked or loose.

  • Carry extra tubing, clamps, and a spare 632445R for rapid on-site swaps.

  • Bundle this switch with inducer motor gaskets and mounting hardware to create a comprehensive service kit.