Flash Codes on York / Coleman Gas Furnace Board

Flash Codes on York / Coleman Gas Furnace Board


FURNACE CONTROL BOARD DIAGNOSTICS

The furnace has built-in, self-diagnostic capability. If a system problem occurs, a blinking LED shows a fault code. The LED can flash red,green or amber to indicate various conditions. It is located behind a clear view port in the blower compartment door.

The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced, as the control is not field repairable.

Flash sequence codes 1 through 11 are as follows: LED will turn on for 1/4 second and off for 1/4 second. This pattern will be repeated the number of times equal to the code. For example, six on flashes equals a number 6 fault code. All flash code sequences are broken by a 2 second off period.

Coleman / York Furnace Flash Code Chart

Flash Code

Result (Meaning)

Fix (Recommended Action)

Slow Green Flash

Normal operation

No action needed

Slow Amber Flash

Normal operation with call for heat

No action needed

Rapid Red Flash

Twinning error, incorrect 24V phasing

Check twinning wiring

Rapid Amber Flash

Flame sense current < 1.5 µA

Clean flame sensor, check gas flow, verify >1.5 µA at test pad

4 Amber Flashes

Y signal from thermostat without G signal

Correct thermostat wiring

1 Red Flash

Flame sensed with no call for heat

Check gas valve for leaks or slow closing

2 Red Flashes

Pressure switch stuck closed

Inspect/replace pressure switch, check wiring

3 Red Flashes

Pressure switch failed to close after inducer energized

Check inducer, vent pipe, hose, or pressure switch

4 Red Flashes

Limit switch open

Check filter, duct sizing, blower speed, firing rate, blower motor; also check fuse on board

5 Red Flashes

Rollout switch open

Reset rollout, check combustion air, inducer, heat exchanger, burners; cycle power after reset

6 Red Flashes

Pressure switch opened 4 times during heat call

Inspect pressure switch, venting, inducer; furnace locks out for 1 hr then retries

7 Red Flashes

Flame not established after 3 tries

Check gas pressure, gas valve, flame sensor, ignitor, burners

8 Red Flashes

Flame lost 5 times during cycle

Inspect gas pressure, flame sensor, gas valve

9 Red Flashes

Reversed line voltage polarity or grounding problem

Verify polarity, grounding, flame probe not shorted

10 Red Flashes

Flame sensed with no call for heat

Inspect gas valve and wiring

11 Red Flashes

Limit switch open >5 minutes (hard lockout)

Likely failed blower motor or wheel; cycle 24 VAC power after correction

12 Red Flashes

Open igniter circuit

Check for loose/disconnected wire or cracked igniter

Steady On Red

Control failure

Replace control board

60-Minute Auto Reset

Watchdog resets lockout after 60 minutes

Temporary protection; correct underlying issue

Flame Sense Levels

Normal ~3.7 µA DC; warning <1.5 µA; lockout <0.1 µA

Verify flame sensor current, clean/replace sensor if low