Flash Codes on York / Coleman Gas Furnace Board
Flash Codes on York / Coleman Gas Furnace Board
FURNACE CONTROL BOARD DIAGNOSTICS
The furnace has built-in, self-diagnostic capability. If a system problem occurs, a blinking LED shows a fault code. The LED can flash red,green or amber to indicate various conditions. It is located behind a clear view port in the blower compartment door.
The control continuously monitors its own operation and the operation of the system. If a failure occurs, the LED will indicate the failure code. If the failure is internal to the control, the light will stay on continuously. In this case, the entire control should be replaced, as the control is not field repairable.
Flash sequence codes 1 through 11 are as follows: LED will turn on for 1/4 second and off for 1/4 second. This pattern will be repeated the number of times equal to the code. For example, six on flashes equals a number 6 fault code. All flash code sequences are broken by a 2 second off period.
Coleman / York Furnace Flash Code Chart
Flash Code |
Result (Meaning) |
Fix (Recommended Action) |
Slow Green Flash |
Normal operation |
No action needed |
Slow Amber Flash |
Normal operation with call for heat |
No action needed |
Rapid Red Flash |
Twinning error, incorrect 24V phasing |
Check twinning wiring |
Rapid Amber Flash |
Flame sense current < 1.5 µA |
Clean flame sensor, check gas flow, verify >1.5 µA at test pad |
4 Amber Flashes |
Y signal from thermostat without G signal |
Correct thermostat wiring |
1 Red Flash |
Flame sensed with no call for heat |
Check gas valve for leaks or slow closing |
2 Red Flashes |
Pressure switch stuck closed |
Inspect/replace pressure switch, check wiring |
3 Red Flashes |
Pressure switch failed to close after inducer energized |
Check inducer, vent pipe, hose, or pressure switch |
4 Red Flashes |
Limit switch open |
Check filter, duct sizing, blower speed, firing rate, blower motor; also check fuse on board |
5 Red Flashes |
Rollout switch open |
Reset rollout, check combustion air, inducer, heat exchanger, burners; cycle power after reset |
6 Red Flashes |
Pressure switch opened 4 times during heat call |
Inspect pressure switch, venting, inducer; furnace locks out for 1 hr then retries |
7 Red Flashes |
Flame not established after 3 tries |
Check gas pressure, gas valve, flame sensor, ignitor, burners |
8 Red Flashes |
Flame lost 5 times during cycle |
Inspect gas pressure, flame sensor, gas valve |
9 Red Flashes |
Reversed line voltage polarity or grounding problem |
Verify polarity, grounding, flame probe not shorted |
10 Red Flashes |
Flame sensed with no call for heat |
Inspect gas valve and wiring |
11 Red Flashes |
Limit switch open >5 minutes (hard lockout) |
Likely failed blower motor or wheel; cycle 24 VAC power after correction |
12 Red Flashes |
Open igniter circuit |
Check for loose/disconnected wire or cracked igniter |
Steady On Red |
Control failure |
Replace control board |
60-Minute Auto Reset |
Watchdog resets lockout after 60 minutes |
Temporary protection; correct underlying issue |
Flame Sense Levels |
Normal ~3.7 µA DC; warning <1.5 µA; lockout <0.1 µA |
Verify flame sensor current, clean/replace sensor if low |